ZnO Blocks

Products | Support | Downloads | Training | Press Releases | About Meiden | Contact | Email | Home
Major Ratings of Meidensha ZnO Blocks
Application for IEC Standard Recommended UR
(kVrms)
Model Dimensions (mm) Range of cirtical operating voltage
(V1mA-DC)
(kV-DC)
Max. residual voltage ratio
(VxkA/V1mA)
(at 8/20s)
Current withstand
capability
Spec. No.
Diameter Height 4/10s (kA) 2ms (A)
5kA Distribution 3.0 ZE32GE20A 31.5±1.0

*36.5±1.0 available
19.5±1.0 4.55 - 5.40 1.78(at 5kA) 65 100 TS-9702A
4.5 ZE32GE30A 29.5±1.0 6.80 - 8.10
6.0 ZE32GE40A 39.5±1.0 9.10 - 10.80
10kA Distribution & Class 1 3.0 ZE42GE20A 42.0±1.0 19.5±1.0 4.55 - 5.40 1.83(at 10kA) 100 250 TS-9802
4.5 ZE42GE30A 29.5±1.0 6.80 - 8.10
6.0 ZE42GE40A 39.5±1.0 9.10 - 10.80
10kA Class 2 1.5 ZE48G11 48.5±1.0 11.5±1.0 2.10 - 2.40 1.79(at 10kA) 100 500 TS-9704A
3.0 ZE48G22 22.0±1.0 4.18 - 4.82
5.0 ZE48G37 37.0±1.0 6.92 - 8.08
10kA Class 3 1.5 ZE64G11 64.5±1.0 11.5±1.0 2.10 - 2.40 1.69(at 10kA) 100 1000 TS-9801A
3.0 ZE64G23 22.5±1.0 4.18 - 4.82
6.0 ZE64G45 44.5±1.0 8.42 - 9.58
20kA Class 4 3.0 ZE74G23 74.5±1.0 22.5±1.0 4.18 - 4.82 1.78(at 20kA) 100 1300 TS-9730
Note:  
a) UR: Rated voltage / MCOV (Maximum continuous operating voltage)
b) Recommended MCOV: UR x 0.8
c) Special purpose blocks are available; For DC use, For under oil use