Vacuum Interrupters (VI)

  • Simplified arc quenching method
  • Simplified construction and high quality
  • No evacuation tube
  • Compact body


Production range:

  • 7.2kV ~ 72kV - 630A ~ 3150A - 20kA ~40kA (for Circuit Breaker)
  • 7.2kV ~ 36kV - 400A, 630A - 3kA / 4kA (for Contactor)
Vacuum Interrupters for Circuit Breaker <50Hz to 60Hz>
Rated
Voltage
Rated
lightning
impulse
voltage
Power
frequency
withstand
Voltage
Rated
Current
Short circuit breaking current with
at least 30~40% DC component and
Interrupter (Outdiameter-Style)
kV kV kV A 12.5kA 16kA 20kA 25kA 31.5kA 40kA 50kA
7.2 60 20 630 M20QC
(52-A)
           
800/1250       M30RA
(94-A)
     
1600/2000         M40SC
(94-A)
   
2500/3150           M50TC
(110-A)
 
12 75 28 630 M31QC
(60-A)
M52QC
(65-B)
  MA61RC**
(94-B)
     
800/1250     M41RC
(73-B)
M51RC
(82-B)
     
1600/2000         M71SC
(94-B)
M81SC
(110-B)
 
2500/3150           M81TC
(132-B)
MA131TC
(150-B)
15 95 38 630 M31QC
(60-A)
M52QC
(65-B)
         
800/1250       MA61RC
(94-B)
     
1600/2000         M71SC
(94-B)
M81SC
(110-B)
 
2500/3150           M81TC
(132-B)
MA131TC
(150-B)
17.5/24 95/125 38/50 630 M52QC*
(65-B)
           
800/1250       M102R
(94-B)
     
1600/2000       M102S
(94-B )
     
2500/3150           M203TCB*
(120-C)
 
36 175 80 630 M83QC*
(65-B)
           
800/1250              
1600/2000       M163SC
(94-C 120-B)
     
2500/3150         M203TCB*
(120-C)
M253TC*
(132-C)
(150-B)
 
* Additional external insulation necessary
** Capacitor Switching (Back-to-Back)

Vacuum Interrupters for Load Break Switch
Rated
Voltage
Rated
lightning
impulse
voltage
Power
frequency
withstand
Voltage
Rated
Current
Short
circuit
making
current
Vl Type
(Dia.-Style)
kV kV kV A kApeak  
12/15.5 95 35 630 50 M01QC
(52-A)
24/27 125 60 630 50 M02QC
(65-B)

Vacuum Interrupters for Auto-Recloser & Fault Interrupter Switch
Rated
Voltage
Rated
lightning
impulse
voltage
Power
frequency
withstand
Voltage
Rated
Current
Short
circuit
breaking
current
Vl Type
(Dia.-Style)
kV kV kV A kA  
15.5 110 50 630 12.5 M31QC
(60-A)
27 125 60 630 12.5 M52QC
(65-B)*
38 150 70 630 12.5 M83QC
(65-B)*

Vacuum Interrupters for Contactor Switch
Rated
Voltage
Rated
lightning
impulse
voltage
Power
frequency
withstand
Voltage
Rated
Current
Short
circuit
breaking
current
Vl Type
(Dia.-Style)
kV kV kV A kA  
6.6 45 20 400 4 5G-1
(52-A)
6.6 45 20 600 6 7.5G
(52-A)

Vacuum Interrupters for Mobile Railway Interrupter Switch
Rated
Voltage
Rated
lightning
impulse
voltage
Power
frequency
withstand
Voltage
Rated
Current
Short
circuit
breaking
current
Short
circuit
making
current
Vl Type
(Dia.-Style)
kV kV kV A kA kA  
18/36 170 70(16.6Hz)
70(50/60Hz)
750(16.6Hz)
450(50/60Hz)
at 18kV
25(16.6Hz)
at 36kV
25(50/60Hz)
at 18kV
62.5(16.6Hz)
163SC
(132-C)